RETROTEC Blower Door 310X (RIPCI)

RETROTEC Blower Door 310X (EU310X-F), 300F enclosure integrity system with Model 300 blower, DM32X pressure gauge, and FanTestic Integrity software, for small enclosures with gas fire suppression.

Consult price

Availability: 11-15 days

Ref: EU310X-F
Request a quote

Description

RETROTEC Blower Door 310X for Building Envelope Integrity

RETROTEC Blower Door 310X in the enclosure integrity version (ref. EU310X-F): a system based on the RETROTEC 300F, featuring a Model 300 fan, a DM32X digital manometer, and a large SmartCloth panel with a large frame, designed to test small enclosures protected by gas-based fire suppression systems.

It tests retention time in chambers up to 120 m³ with inert agents and up to 240 m³ with halocarbon agents, and allows for testing relief valves in volumes up to 40 m³ with an inert agent. Its compact design makes it easy to transport, even by plane.

With FanTestic Integrity, the Blower Door 310X calculates air retention time, peak pressure, and minimum vent area, and generates reports in Word that can be exported to Excel.

Key Features of the RETROTEC Blower Door 310X

  • For small containers: Storage capacity of up to 120 m³ (inert substances) and 240 m³ (halocarbons).
  • DM32X Pressure Gauge: 5.5-inch 1080p HD OLED display with Gorilla Glass, real-time pressure graph, data logging, and digital signal processing.
  • FanTestic Integrity Software: Automatic calculation of retention, peak pressure, and vent area, with reports in Word and export to Excel.
  • Compact and portable: Designed to be transported to any facility, even by plane.
  • Connectivity: The DM32X features USB-C, Bluetooth with a 10-meter range, and Wi-Fi.
  • Large SmartCloth Panel: SmartCloth fabric panel with a large aluminum frame.

Applications of the Blower Door 310X

  • Leak Test (Door Fan Test) for Enclosures with Inert Gas or Halocarbon Fire Suppression Systems
  • Calculation of the retention time of the extinguishing agent
  • Peak Pressure Analysis and Sizing of the Venting Area
  • Inspection of Installed Pressure Relief Valves

Compatibility: The Model 300 fan is compatible with the RETROTEC DM32X and DM32 pressure gauges (model “300”); it is not compatible with the DM-2 pressure gauge.

Ref. EU310X-F

Technical data

Measurement and Analysis

FanRETROTEC Model 300
Pressure GaugeDM32X, 2 channels
Maximum retention volume – inert agent120 m³ (4,000 ft³)
Maximum retention volume – halocarbon agent240 m³ (8,000 ft³)
Maximum test volume for gates – inert agent40 m³ (1,000 ft³)
SoftwareFanTestic Integrity
Software Calculation MethodsNFPA 2001 (2022), ISO 14520 (2015), EN 15004 (2019)
System CalibrationEnclosure Integrity

Display and Image

DM32X Display5.5-inch 1080p HD OLED, Gorilla Glass
Touch TechnologyCapacitive multi-touch
VisualizationReal-time pressure graph; horizontal or vertical orientation

Feeding

Fan VoltageConfigurations: 110 V (50 Hz), 120 V, 240 V with Type E plug, and 240 V with Type G plug
DM32X BatteryRechargeable lithium polymer battery
Battery Life of the DM32XApprox. 8.5 hours
Battery LifeUp to 4 years or 6,000 cycles
DM32X LoadUSB-C, 3 A with AC adapter; fully charged in approx. 4 hours

General

BrandRETROTEC
ReferenceEU310X-F
Base System300F Fire System [Enclosure Integrity]
DoorLarge SmartCloth panel with a large 50″ aluminum frame
Doorway with a large frame81–130 cm wide × 150–277 cm high
Weight of the DM32X0.39 kg
DM32X ConnectivityUSB-C, Bluetooth 4.2 (10 m), Wi-Fi 802.11 a/g/n/ac, Ethernet
DM32X SystemAndroid 11

Compatible Accessories

SoftwareFanTestic Integrity, licenses for 1, 2, or 3 fans
Pressure gauges compatible with the 300 ventilatorDM32X, DM32
Smoke generatorsPower Tiny, Tiny S

Related products