FLIR DM284 - Thermographic Multimeter with IGM

This product is discontinued.
This is the model that replaces it:
FLIR DM266

FLIR DM286 Thermographic Multimeter with METERLiNK® data logging/application and IGM

989,00+ VAT

Description

FLIR DM284

Multimeter with thermal camera

Troubleshoot problems quickly with the FLIR DM284 Thermal Imaging Multimeter with Thermal Imager

The FLIR DM284 thermographic multimeter is a unique device in its category, as it can detect anomalies that are impossible for other multimeters on the market to detect. The FLIR DM284 thermographic multimeter is the result of combining a professional digital with real RMS with a thermographic detector, so that it is able to detect hot spots and indicate the precise location of a hot spot or area at higher temperature, where it is possible that there is an electrical anomaly. This new methodology, developed by FLIR, is known as IGM: Infrared Guided Measurement.

The FLIR DM284 Thermographic Multimeter is a comprehensive and practical tool, ensuring that you always have an electrical analysis tool and a thermal imaging camera with 160×120 pixel resolution in the same hand. You can visually identify electrical problems without direct contact with the target, the infrared-guided measurement helps you to quickly remedy the situation.

Easily solve complex problems
With 18 measurement functions, including True RMS, LoZ, and NCV, you can identify potential problems with reliable readings at all times, even in the most complex situations. The DM284 infrared camera multimeter also includes a thermocouple input and allows you to view thermal and electrical measurements simultaneously.

Ref.DM284

FLIR DM284 - Thermal Imaging Multimeter with IGM™

FLIR IGM™, Infrared Guided Measurement What is it?

Technical Data

Thermal imaging

Detector type
FLIR Lepton; micro-bolometer focal plane array (FPA)
IR imaging resolution (H × V)
160 × 120 pixels
IR imaging field of view (H × V)
57° × 44°
IR imaging spectral response
8-14 μm
Thermal sensitivity
150 mK
IR image capture frequency
9 Hz
IR image color palettes
Rainbow, Iron, Gray scale
Laser pointer type
Class I (red)
Laser pointer power
<0.4 mW
IR temperature measurement range
-10 to 150°C (14 to 302°F)
Over- and under-range indication
OL
Temperature reading stabilization
Dashes are displayed for approximately 30 seconds as the temperature reading stabilizes
IR temperature resolution
0.1°C (0.1°F)
IR temperature accuracy
±3°C (5.4°F) or ± 3% of the reading (whichever is greater) for >25°C (77°F), ±5°C -10°C to 25°C (14°F to 77°F)
Distance-to-spot (D:S) ratio
30:1
Emissivity adjustment
0.95 maximum, 4 presets plus a custom setting (0.10-0.99)
Targeting
Displayed cross-hairs pinpoint the center of the measurement spot
Hold
Image with measurement

Electrical measurement

Maximum voltage
1000 V DC or 1000 V AC RMS
Display count
6000
Frequency counter
  • 100.00 Hz ± (0.1% + 2D)
  • 1000.0 Hz ± (0.1% + 2D)
  • 10,000 kHz ± (0.1% + 2D)
  • 100.00 kHz ± (0.1% + 2D)
Resistance
  • 600.0 Ω ± (0.9% + 5D)
  • 6.000 kΩ ± (0.9% + 2D)
  • 60.00 kΩ ± (0.9% + 2D)
  • 600.0 kΩ ± (0.9% + 2D)
  • 6.000 MΩ ± (0.9% + 2D)
  • 50.00 MΩ ± (3.0% + 5D)
Continuity check
600.0 Ω ± (0.9% + 5D)
Diode test
1.500 ± (0.9% + 2D)
Capacitance
  • 1000 nF ± (1.9% + 5D)
  • 10.00 µF ± (1.9% + 2 digits)
  • 100.0 µF ± (0.9% + 2 digits)
  • 1,000 mF ± (0.9% + 2 digits)
  • 10.00 mF ± (0.9% + 2 digits)
  • 40.00 mF ± (2.0% + 20 digits)
Temperature, type K thermocouple
  • -40 to 752.0°F DMM ± (1.0% + 5.4°F)/ IGM ± (1.0% + 9°F)
  • -40 to 400°C DMM ± (1.0% + 3°C)/ IGM ± (1.0% + 5°C)
Measuring rate
3 samples per second

Meter data

Category rating
CAT IV-600 V, CAT III-1000 V
IP rating
IP54
Drop test
3M
Warranty
Calibration cycle
Once per year, recommended

Certifications

Certifications
UL, CE, FCC, CB
Safety standards compliance
IEC 61010-1 CAT IV-600 V, CAT III-1000 V

Power system

Power requirements
4 × 1.5 V AAA alkaline batteries. Or optional TA04 rechargeable lithium polymer rechargeable battery system.
Battery life, alkaline batteries
Approximately 5 hours DMM or 2 hours IGM
Battery life, lithium polymer batteries
Approximately 30 hours DMM or 10 hours IGM
Auto power off
Default: 20 minutes

Environmental data

Operating ambient temperatures and relative humidity (RH)
–10 to 30°C (14 to 86°F), <85% RH 30 to 40°C (86 to 104°F), <75% RH 40 to 50°C (104 to 122°F), <45% RH
Storage temperature and RH
-20 to 60°C (-4 to 140°F), 0-80% RH (without batteries)
Temperature coefficient
0.1 × (specified accuracy)/°C, <18°C (64.4°F) , >28°C (82.4°F)
Operating altitude
2000 m (6560 ft.)
Pollution degree
2
EMC
EN61326-1
Shock vibration
Per MIL-PRF-28800F Class 2

Meter physical data

Weight
536 g (18.9 oz.)
Dimensions (L × W × H)
200 mm × 95 mm × 49 mm (7.9 in. × 3.7 in. × 1.9 in.)
Material
PC/ABS
Color
Gray, black, and blue

Shipping information

Packaging type
Color box with a view of theproduct in the clamshell
Packaging contents
DM284 FLIR meter, TA82 premium test leads, TA70 alligator clips, TA60 thermocouple probe with adapter, TA84 test lead holder storage/tripod accessory, 4 × AAA Energizer batteries, English-only quick start guide
Packaging weight
1.2 kg (2.6 lb.)
Packaging dimensions (H × W × L)
32 cm × 14 cm × 11 cm (12.6 in. × 5.5 in. × 4.3 in.)
Carton weight
15 kg (33 lb.)
Carton dimensions (H × W × L)
65 cm × 30 cm × 56 cm (25.6 in. × 11.8 in. × 22.0 in.)
Carton quantity
12
EAN-13
0793950372845
UPC-12
793950372845
Country of origin
Taiwan
Tariff Code
9030310000

Box contents

  • DM284 Thermographic multimeter
  • Silicone test leads
  • Alligator clips
  •  Thermocouple probe with adapter
  • Test cable support accessory
  • 4 AAA batteries

Related products